HR1110S 10KVA
INVT UPS HR1110S 10KVA
Online,Rackmount,pure sine wave,10KVA/9KW,192VDC,with 16pcs 12V/9AH batteries HR11 series is online double-conversion UPS with full DSP control technology. With 19”standard rack design, HR11Series Rack Online UPS 1-10kVA (220V/2ND/240V))
Technical Specs
INPUT
- Cold Start YES, default frequency=50Hz or settable
- Acceptable Input Voltage 50%~125%(220VAC/230VAC/240VAC)
- 100% load@80%~125%
- 90% load@70%~80%
- 80% load@60%~70%
- 65% load@50%~60%
- Phase Single phase in,single phase out
- Transfer Voltage Range
- Line low transfer 110VAC/115VAC/120VAC
- Line low recovery 116VAC/122VAC/127VAC
- Line high transfer 275VAC/288VAC/300VAC
- Line high recovery 268VAC/279VAC/291VAC
- Input Power Factor ≥0.99
- Input Frequency Range 40Hz – 70Hz
- Generator Support Any Generator.
OUTPUT
- Frequency adaptable Settable
- Power
- Power(kVA) max 10
- Power(kW) max 9
- Output Voltage
- Waveform Pure sine wave
- Nominal voltage 220/230/240VAC
- Voltage regulation ± 1 %
- Transient response ≤5% (50% – 100% -50%)
- Transient recovery ≤15ms (0% – 100% -0%)
- Voltage distortion ≤1% THD, linear load
- ≤5% THD, non-linear load
Output Frequency
- Synchronization range settable,±3Hz default
- Slew rate 0.5~5Hz/s,2Hz/s default
- Battery mode (50±0.05) Hz
- Transfer Time
- Line mode to battery mode 0
- Inverter to bypass 0
Efficiency
- Line mode with battery full charged 93.0%
- ECO mode 98.0%
- Battery mode 92.0%
- Noise <48dB@<70%load,70%load;1m away
- Overload Capability (Line Mode) 110%: Transfer to bypass after 10 mins
- 130%: Transfer to bypass after 1 min
- 150%: Transfer to bypass after 30s, shutdown after 1 min.(Line mode)
- Overload Capability (Battery Mode) 110%: Shutdown after 10mins (Battery mode)
- 125%:Shutdown after 10s(Battery mode)
- >125%: Shutdown after 1s (Battery mode)
- Crest Ratio 3:1
BATTERY
- Rating/Type 12VDC/9Ah
- Quantity 16
- DC Voltage 192VDC
- Back-up Time 3.5mins @80% load
- Battery-Low Voltage (176±3)VDC
Charger
- Charging voltage (220±1%)VDC
- Charging current (max) 1A
- Charging time 8h recharge to 90%
- Leakage current <1mA
- INDICATOR & ALARM
- Display LED+LCD
Alarm
INTERFACE
- Smart RS232 Standard Cable support INVT Power Monitor Software
- B type USB(optional) Standard Cable support INVT Power Monitor Software
- EPO Remoted EPO function for customer. Short to activate
- Dry Contactor(optional) DB9 type and phoenix terminal type for selection. (6 output ports, 1 input port) UPS fault alarm, general alarm, bypass mode, UPS normal mode, battery low voltage alarm, utility failure alarm, remoted shutdown.
- SNMP(optional) Power Managment from SNMP Manager and Web Browser
- Option SNMP, USB, Dry Contactor(AS400),Parallel Kit, ECO Kit, External Battery Cable(standard model), Maintenance Bypass, Maintenance Bypass Detecting Kit
- Reserved function Can be designed as deffirent function according to customer’s appliction