INPUT

  • Cold Start:  YES, default frequency=50Hz or settable
  • Acceptable Input Voltage:
  • 110VAC~288VAC
  • 100% load@>176VAC
  • 80% load@>154VAC
  • 70% load@>132VAC
  • 50% load@>110VAC

Phase :Single phase in,single phase out

Transfer Voltage Range:

  •    (200VAC/208VAC/220VAC/230VAC/240VAC)
  •     -Line low transfer 110VAC
  •     -Line low recovery 121VAC
  •     -Line high transfer 288VAC
  •     -Line high recovery 281VAC

Input Current

  • Rating(nominal input voltage) : 14.4A
  • Input Power Factor ≥0.97
  • Input Frequency Range 40~70Hz

OUTPUT

Frequency adaptable Settable

Power

  1.  Power(kVA) max : 3
  2.  Power(kW) max3 : 2.7(2.4 for 200VAC/208VAC)

Output Voltage

  •     Waveform(Bat. Mode) Pure Sine Wave
  •     Nominal voltage 200/208/220/230/240VAC
  •     Voltage regulation ± 1 %
  •     Transient response   ≤5% (0% – 100% -0%)
  •     Transient recovery ≤30ms (0% – 100% -0%)
  •     Voltage distortion ≤2% THD, linear load
  • ≤ 5% THD, non-linear load

Output Frequency

  •  Synchronization range ±5Hz default
  •  Battery mode (50±0.1) Hz default
  • Transfer Time
  •  Line mode to battery mode 0
  •  Inverter to bypass 2ms

Efficiency

  •    Line mode with battery full charged : 88%@100% load, 90%@50% load
  •    ECO mode: 97.0%
  •    Battery mode: 87%@100% load, 89%@50% load
  •    Noise(1m away): <45dB@<60%load,60%load
  • Overload Capability(Inverter) 105%~130%: Transfer to bypass after 1 mins.
  • 150%: Transfer to bypass after 30s
  • Overload Capability(Battery Mode) 105%~130%:shutdown after 10s
  • 150%:shutdown after 5s
  • Overload Capability (Bypass Mode) <130%: Long time
  • >130%&<150%:Shutdown after 10min
  • >150%&<180%:Shutdown after 5 seconds
  • Crest Ratio 3:1

BATTERY

  • Rating/Type: 12VDC/7Ah
  • Quantity: 8
  • DC Voltage: 96VDC
  • Back-up Time: 5.5mins @80% load
  • Battery-Low Voltage: 88VDC~94VDC depending on load

INDICATOR & ALARM

  •     Display: LED+LCD
  •     Alarm two short one long
  •     Fault Continuous beeping

INTERFACE

  •     Smart RS232 Standard Cable support INVT Power Monitor Software
  •     SNMP(option) Power Managment from SNMP Manager and Web Browser

OPTION

  • Intelligent Kits DB9 port, dry contact
  • USB B-type USB port
  • SNMP Kits pluggable type
  • Leakage current :<1mA

Charger

  •   Charging voltage : float:109VDC/boost:112VDC
  •   Charging current (max) : 1A
  •   Charging time : 8h recharge to 90%