HR1106S 6KVA

INVT UPS HR1106S 6KVA, Online,Racktower type,pure sine wave,6KVA/5.4KW,192VDC,with 16pcs 12V/7AH

Technical Specs

INPUT

  • Cold Start YES, default frequency=50Hz or settable
  • Acceptable Input Voltage 50%~125%(220VAC/230VAC/240VAC)
  • 100% load@80%~125%
  • 90% load@70%~80%
  • 80% load@60%~70%
  • 65% load@50%~60%
  • Phase :Single phase in,single phase out
  • Transfer Voltage Range
  • Line low transfer 110VAC/115VAC/120VAC
  • Line low recovery 116VAC/122VAC/127VAC
  • Line high transfer 275VAC/288VAC/300VAC
  • Line high recovery 268VAC/279VAC/291VAC
  • Input Power Factor ≥0.99
  • Input Frequency Range 40Hz – 70Hz
  • Generator Support Any Generator.

OUTPUT

  • Frequency adaptable Settable

Power

  • Power(kVA) max 6
  • Power(kW) max 5.4

Output Voltage

  • Waveform Pure sine wave
  • Nominal voltage 220/230/240VAC
  • Voltage regulation ± 1 %
  • Transient response   ≤5% (50% – 100% -50%)
  • Transient recovery ≤15ms (0% – 100% -0%)
  • Voltage distortion ≤1% THD, linear load
  • ≤ 5% THD, non-linear load

Output Frequency

  • -Synchronization range settable,±3Hz default
  • Slew rate 0.5~5Hz/s,2 Hz/s default
  • -Battery mode (50±0.05) Hz

Transfer Time

  • -Line mode to battery mode 0
  • -Inverter to bypass 4ms

Efficiency

  • -Line mode with battery full charged 93.0%
  • -ECO mode 98.0%
  • -Battery mode 92.0%
  • Noise <48dB@<70%load,70%load;1m away
  • Overload Capability (Line Mode) 110%: Transfer to bypass after 10 mins.
  • 130%: Transfer to bypass after 1 min
  • 150%: Transfer to bypass after 30s, shutdown after 1 min.(Line mode)
  • Overload Capability (Battery Mode) 110%: Shutdown after 10mins (Battery mode)
  • 125%:Shutdown after 10s(Battery mode)
  • >125%: Shutdown after 1s (Battery mode)
  • Crest Ratio 3:1

BATTERY

  • Rating/Type:12VDC/7Ah
  • Quantity:16
  • DC Voltage:192VDC
  • Back-up Time :4mins @80% load
  • Battery-Low Voltage: (176±3)VDC

Charger:

  • Charging voltage:(220±1%)VDC
  • Charging current (max): 1A
  •  Charging time:7h recharge to 90%
  • Leakage current: <1mA
  • INDICATOR & ALARM:
  • Display:LED+LCD

Alarm:

  • Fault:Continuous beeping

INTERFACE

  • Smart RS232 Standard Cable support INVT Power Monitor Software
  • B type USB(optional) Standard Cable support INVT Power Monitor Software
  • EPO Remoted EPO function for customer. Short to activate
  • Dry Contactor(optional) DB9 type and phoenix terminal type for selection. (6 output ports, 1 input port) UPS fault alarm, general alarm, bypass mode, UPS normal mode, battery low voltage alarm, utility failure alarm, remoted shutdown.
  • SNMP(optional) Power Managment from SNMP Manager and Web Browser
  • Option SNMP, USB, Dry Contactor(AS400),Parallel Kit, ECO Kit, External Battery Cable(standard model), Maintenance Bypass, Maintenance Bypass Detecting Kit
  • Reserved function Can be designed as different function according to customer’s application