INVT UPS HR1106S 6KVA, Online,Racktower type,pure sine wave,6KVA/5.4KW,192VDC,with 16pcs 12V/7AH
Technical Specs
INPUT
Cold Start YES, default frequency=50Hz or settable
Acceptable Input Voltage 50%~125%(220VAC/230VAC/240VAC)
100% load@80%~125%
90% load@70%~80%
80% load@60%~70%
65% load@50%~60%
Phase :Single phase in,single phase out
Transfer Voltage Range
Line low transfer 110VAC/115VAC/120VAC
Line low recovery 116VAC/122VAC/127VAC
Line high transfer 275VAC/288VAC/300VAC
Line high recovery 268VAC/279VAC/291VAC
Input Power Factor ≥0.99
Input Frequency Range 40Hz – 70Hz
Generator Support Any Generator.
OUTPUT
Frequency adaptable Settable
Power
Power(kVA) max 6
Power(kW) max 5.4
Output Voltage
Waveform Pure sine wave
Nominal voltage 220/230/240VAC
Voltage regulation ± 1 %
Transient response ≤5% (50% – 100% -50%)
Transient recovery ≤15ms (0% – 100% -0%)
Voltage distortion ≤1% THD, linear load
≤ 5% THD, non-linear load
Output Frequency
-Synchronization range settable,±3Hz default
Slew rate 0.5~5Hz/s,2 Hz/s default
-Battery mode (50±0.05) Hz
Transfer Time
-Line mode to battery mode 0
-Inverter to bypass 4ms
Efficiency
-Line mode with battery full charged 93.0%
-ECO mode 98.0%
-Battery mode 92.0%
Noise <48dB@<70%load,70%load;1m away
Overload Capability (Line Mode) 110%: Transfer to bypass after 10 mins.
130%: Transfer to bypass after 1 min
150%: Transfer to bypass after 30s, shutdown after 1 min.(Line mode)
Overload Capability (Battery Mode) 110%: Shutdown after 10mins (Battery mode)
125%:Shutdown after 10s(Battery mode)
>125%: Shutdown after 1s (Battery mode)
Crest Ratio 3:1
BATTERY
Rating/Type:12VDC/7Ah
Quantity:16
DC Voltage:192VDC
Back-up Time :4mins @80% load
Battery-Low Voltage: (176±3)VDC
Charger:
Charging voltage:(220±1%)VDC
Charging current (max): 1A
Charging time:7h recharge to 90%
Leakage current: <1mA
INDICATOR & ALARM:
Display:LED+LCD
Alarm:
Fault:Continuous beeping
INTERFACE
Smart RS232 Standard Cable support INVT Power Monitor Software
B type USB(optional) Standard Cable support INVT Power Monitor Software
EPO Remoted EPO function for customer. Short to activate
Dry Contactor(optional) DB9 type and phoenix terminal type for selection. (6 output ports, 1 input port) UPS fault alarm, general alarm, bypass mode, UPS normal mode, battery low voltage alarm, utility failure alarm, remoted shutdown.
SNMP(optional) Power Managment from SNMP Manager and Web Browser